• DocumentCode
    3259566
  • Title

    Leakage current harmonic components: Indexes to insulator ageing

  • Author

    Bashir, Nouruddeen ; Ahmad, Hussein

  • Author_Institution
    Fac. of Electr. Eng., Univ. Teknol. Malaysia, Skudai, Malaysia
  • fYear
    2009
  • fDate
    23-26 Jan. 2009
  • Firstpage
    1
  • Lastpage
    5
  • Abstract
    This paper reports an investigation carried out in the laboratory on 45 units of glass insulator samples. The insulator units comprise of 5 groups; new and field-aged insulators with different ageing period (>30, 20, 15 and <10 years) from 132 kV transmission line. The results revealed a correlation between the ratio of the 3rd and 5th harmonic amplitudes with the degree of degradation of the field-aged insulators. This correlation was validated with Dissipation factor (tan ¿) tests and flashover voltage measurements carried out on the insulators. All the results were in good agreement. Thus this finding suggests the viability of monitoring and diagnosing ageing insulators in situ.
  • Keywords
    ageing; flashover; glass; insulators; leakage currents; field-aged insulators; flashover voltage measurements; glass insulator; harmonic amplitudes; insulator ageing; leakage current harmonic components; transmission line; voltage 132 kV; Aging; Degradation; Flashover; Glass; Insulation; Insulator testing; Laboratories; Leakage current; Monitoring; Voltage measurement; ageing; flashover; glass insulator; harmonics; leakage current;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    TENCON 2009 - 2009 IEEE Region 10 Conference
  • Conference_Location
    Singapore
  • Print_ISBN
    978-1-4244-4546-2
  • Electronic_ISBN
    978-1-4244-4547-9
  • Type

    conf

  • DOI
    10.1109/TENCON.2009.5396216
  • Filename
    5396216