  • Abstract
    ACSR-OC(aluminum stranded conductors steel reinforced outdoor linked wires) wire is composed of the three type metals(aluminum, zinc, iron) and contacted with each other. So ACSR-OC wire is liable to occur the electrolytic corrosion when the conductive water solution exists. We carried out the test about the used ACSR-OC wires above 10 years in the real site and the new products in order to investigate the performance characteristic changed by a salt. Also we conducted the mechanical strength test, the component analysis(SEM) and the microscope observation of each samples. As a result of experiment, A component as a Al, O, Cl, Na has been detected in the wire surface of the used line. Also the wire has been already corroded or underway, therefore the mechanical strength of wire has been reduced.
  • Keywords
    aluminium; corrosion; iron; mechanical strength; steel; wires; zinc; Al; Fe; SEM; Zn; aluminum; aluminum insulation wire; aluminum stranded conductors steel reinforced outdoor linked wires; component analysis; conductive water solution; electrolytic corrosion; iron; mechanical strength test; seashore area; zinc; Aluminum; Cable insulation; Conductors; Corrosion; Iron; Microscopy; Steel; Testing; Wire; Zinc;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulating Materials, 2008. (ISEIM 2008). International Symposium on
  • Conference_Location
    Mie
  • Print_ISBN
    978-4-88686-005-7
  • Electronic_ISBN
    978-4-88686-006-4
  • Type

    conf

  • DOI
    10.1109/ISEIM.2008.4664576
  • Filename
    4664576