DocumentCode
3268180
Title
Evaluation of the grounding circuit measurements for stator ground-fault location of synchronous generators
Author
Blanquez, Francisco R. ; Rebollo, Emilio ; Platero, Carlos A.
Author_Institution
Electr. Eng. Dept., Polytech. Univ. of Madrid, Madrid, Spain
fYear
2013
fDate
1-3 Nov. 2013
Firstpage
229
Lastpage
233
Abstract
Locating stator-winding ground faults accurately is a very difficult task. In this paper the grounding circuit measurements are evaluated in order to obtain information about the stator ground-fault location in synchronous generators. In power generators grounded through a high impedance, the relation between the neutral voltage and the phase voltage provide a first estimation of the fault location. The location error by using this ratio depends on the fault resistance and the value of the capacitance to ground of the stator winding. However, the error added by ignoring the value of the fault resistance is the most relevant term. This location estimation and the location error have been evaluated through the data of a real synchronous machine.
Keywords
capacitance; earthing; electric resistance; fault location; stators; synchronous generators; capacitance; fault location error; fault resistance; grounding circuit measurements; neutral voltage; phase voltage; power generator; stator winding ground fault location estimation; synchronous generator; synchronous machine; Circuit faults; Estimation; Grounding; Radio frequency; Resistance; Stator windings; Stator ground fault; fault location; generator protection;
fLanguage
English
Publisher
ieee
Conference_Titel
Environment and Electrical Engineering (EEEIC), 2013 13th International Conference on
Conference_Location
Wroclaw
Print_ISBN
978-1-4799-2802-6
Type
conf
DOI
10.1109/EEEIC-2.2013.6737913
Filename
6737913