Abstract :
This paper will describe a new algorithm for detecting the out of step and power swing condition. This algorithm, which is based on continuous impedance monitoring, doesn´t require a blinder or concentric characteristics. Therefore no settings are needed. The algorithm continuously monitors the speed and the shape of the impedance trajectory and will immediately see the start of a power swing cycle or an out of step condition. This detection also enables the algorithm to detect fast swing cycles with swing frequencies up to 7 Hz. Solution to three pole fault detection is by a ripple on space vector
Keywords :
fault diagnosis; power system faults; continuous impedance monitoring; out of step blocking algorithm; power swing frequency; space vector ripple; three pole fault detection; Change detection algorithms; Electrical fault detection; Fault detection; Frequency; Impedance; Logic; Power system faults; Protection; Protective relaying; Voltage;