• DocumentCode
    3279247
  • Title

    On-site Diagnostic Tests on Polymer Insulated Cables Using Depolarization Current Measurements

  • Author

    Dakka, M. Abou ; Bulinski, A. ; Bamji, S.

  • Author_Institution
    National Research Council of Canada, Ottawa, Ontario, Canada, K1A 0R6. E-mail: mahmoud. abou-dakka@nrc-cnrc.gc.ca
  • fYear
    2007
  • fDate
    8-13 July 2007
  • Firstpage
    725
  • Lastpage
    728
  • Abstract
    Amodified technique of depolarization current measurements encompassing monitoring of high speed depolarization processes was used to perform diagnostic tests on polymeric cable insulation operating under diverse environmental conditions and voltage levels. The high frequency characteristics were compared with those of the slower depolarization processes commonly obtain during on-site tests. Both the high and low frequency measurements showed a consistent correlation with the operating conditions of the cable insulation. It was observed that the low frequency characteristics were dependent on the duration of the dc poling time but only if the insulation was deteriorated, especially with water trees. Unaged and relatively new insulation did not show such behavior. The majority of the field tests were performed with a relatively low dc voltage of only 1 kV or less and under very adverse environmental conditions, with temperatures as low as ¿30°C.
  • Keywords
    Cable insulation; Cables; Condition monitoring; Current measurement; Frequency; Insulation testing; Performance evaluation; Plastic insulation; Polymers; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Solid Dielectrics, 2007. ICSD '07. IEEE International Conference on
  • Conference_Location
    Winchester, UK
  • Print_ISBN
    1-4244-0750-8
  • Electronic_ISBN
    1-4244-0751-6
  • Type

    conf

  • DOI
    10.1109/ICSD.2007.4290916
  • Filename
    4290916