• DocumentCode
    3283612
  • Title

    Test and application study of allowable dynamic carrying capacity on transmission lines

  • Author

    Wenxuan, Wu ; Jinxiang, Chen ; Liqin, Lin

  • Author_Institution
    Electr. Power Res. Inst., FuJian Electr. Power Co. Ltd., Fuzhou, China
  • fYear
    2011
  • fDate
    15-17 April 2011
  • Firstpage
    4560
  • Lastpage
    4564
  • Abstract
    Morgan theoretical formula current in the wire is right under steady state conditions, yet the transmission line load current and the meteorological conditions are always changing in a dynamic, so there is much error between the theoretical values and the actual dynamic measurement value upon the measured wire temperature and meteorological parameters.This article firstly deduce the transmission line carrying capacity formula of Morgan under the dynamic conditions, verifying its correctness via several field trials.And when Current draw large changes in the wire, dynamic fast rise time of the commonly used models wire temperature is longer than 30 min, which is much longer than the common allowed overload time. In short, with the application of meteorological parameters of practical engineering and on-line temperature measurement Device, it can effectively improve transmission line capacity. Calculations of the actual case show that most of the overall transportation capacity line can be increased by 10% to 20% or more, which is of great significance for improving the transmission capacity and network incident handling.
  • Keywords
    power system measurement; power transmission lines; temperature measurement; Morgan theoretical formula; allowable dynamic carrying capacity; meteorological conditions; meteorological parameters; network incident handling; on-line temperature measurement; practical engineering; transmission capacity; transmission line capacity; transmission line carrying capacity formula; transmission line load current; transmission lines; wire temperature; Measurement uncertainty; Power transmission lines; Temperature measurement; Time measurement; Transmission line measurements; Wires; Morgan formula; conductor short-time temperature-rise; current carrying capacity; dynamic;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electric Information and Control Engineering (ICEICE), 2011 International Conference on
  • Conference_Location
    Wuhan
  • Print_ISBN
    978-1-4244-8036-4
  • Type

    conf

  • DOI
    10.1109/ICEICE.2011.5777776
  • Filename
    5777776