DocumentCode
3298979
Title
Sheath voltage calculations in long medium voltage power cables
Author
Gouramanis, Kostas V. ; Kaloudas, C.G. ; Papadopoulos, Theofilos A. ; Papagiannis, Grigoris K. ; Stasinos, Konstantinos
Author_Institution
Dept. of Electr. & Comput. Eng., Aristotle Univ. of Thessaloniki, Thessaloniki, Greece
fYear
2011
fDate
19-23 June 2011
Firstpage
1
Lastpage
7
Abstract
This paper investigates the operation of single core underground medium voltage cables connected in parallel. The examination is based on an existing power cable arrangement connecting a 38 MW wind farm with the transmission grid. The cable arrangement consists of nine single core cables connected in parallel to form a triple 3-phase system. Several connection scenarios such as the earthing of the cable sheaths at one or both ends and the application of sheath cross-bondings are examined. Various simulation parameters are also investigated such as the grounding resistance of the cable sheaths and the number of the cable sheath transpositions. The respective voltages and currents induced on the cable sheaths are calculated under steady-state and short circuit conditions.
Keywords
cable sheathing; earthing; fault diagnosis; power cables; power grids; underground cables; wind power plants; cable sheath transpositions; earthing; grounding resistance; power 38 MW; power cable arrangement; sheath cross-bondings; sheath voltage calculations; short circuit conditions; single core underground medium voltage cables; steady-state conditions; transmission grid; triple 3-phase system; wind farm; Cable insulation; Cable shielding; Grounding; Integrated circuit modeling; Power cables; Steady-state; Wind farms; ATP/EMTP; cross-bonding; sheath currents; underground power cables;
fLanguage
English
Publisher
ieee
Conference_Titel
PowerTech, 2011 IEEE Trondheim
Conference_Location
Trondheim
Print_ISBN
978-1-4244-8419-5
Electronic_ISBN
978-1-4244-8417-1
Type
conf
DOI
10.1109/PTC.2011.6019234
Filename
6019234
Link To Document