DocumentCode
330491
Title
Computation of AC critical flashover voltage of insulators covered with ice
Author
Zhang, J. ; Farzaneh, M.
Author_Institution
Quebec Univ., Chicoutimi, Que., Canada
Volume
1
fYear
1998
fDate
18-21 Aug 1998
Firstpage
524
Abstract
Using a high-speed frame camera, the behavior of the partial arc on triangular ice samples was studied under AC voltage. The relationship between the radius of partial arc root and the leakage current was determined. Based on the model developed in our previous studies and the results obtained in the present work, the model was improved and used to calculate the flashover voltage of ice-covered insulators. This model takes into account the variation of arc root radius with leakage current. It was shown that there was a good concordance between the results calculated from the model and the laboratory results
Keywords
arcs (electric); flashover; ice; insulator testing; leakage currents; AC critical flashover voltage; high-speed frame camera; ice covered insulators; ice-covered insulators; leakage current; partial arc behaviour; partial arc root radius; Cameras; Computer industry; Equations; Flashover; Ice surface; Insulation; Laboratories; Leakage current; Pollution; Voltage;
fLanguage
English
Publisher
ieee
Conference_Titel
Power System Technology, 1998. Proceedings. POWERCON '98. 1998 International Conference on
Conference_Location
Beijing
Print_ISBN
0-7803-4754-4
Type
conf
DOI
10.1109/ICPST.1998.729019
Filename
729019