Title :
Wide Area Monitoring Experiences in Norway
Author :
Leirbukt, A.B. ; Gjerde, J.O. ; Korba, P. ; Uhlen, K. ; Vormedal, L.K. ; Warland, L.
Author_Institution :
ABB, Oslo
fDate :
Oct. 29 2006-Nov. 1 2006
Abstract :
In this paper, a wide area monitoring system (WAMS) for the 420 kV Norwegian bulk transmission grid has been evaluated. The robustness of the PMU measurements has been demonstrated by a direct comparison of phasor information from the PMUs and a state estimator (EMS). The paper highlights benefits of both off-line and on-line WAMS applications: a method for real-time detection of power oscillations, as well as the use of WAMS as input to power system stabilizers (PSS), is presented
Keywords :
power grids; power system measurement; power system stability; power system state estimation; power transmission faults; 420 kV; EMS; Norwegian bulk transmission grid; PMU; PSS; WAMS; phasor measurement unit; power oscillations; power system stabilizer; state estimator; wide area disturbance; wide area monitoring system; Control systems; Monitoring; Phase measurement; Phasor measurement units; Power system dynamics; Power system measurements; Power system security; Power system stability; Research and development; Wide area measurements;
Conference_Titel :
Power Systems Conference and Exposition, 2006. PSCE '06. 2006 IEEE PES
Conference_Location :
Atlanta, GA
Print_ISBN :
1-4244-0177-1
Electronic_ISBN :
1-4244-0178-X
DOI :
10.1109/PSCE.2006.296331