DocumentCode :
3314273
Title :
Analytical solution and scaled model of a unipolar HVDC transmission line
Author :
Li, Xin ; Raghuveer, M.R. ; Ciric, I.R.
Author_Institution :
Dept. of Electr. & Comput. Eng., Manitoba Univ., Winnipeg, Man., Canada
fYear :
1999
fDate :
1999
Firstpage :
142
Abstract :
Existing analytical solutions for the ionized field of a unipolar HVDC transmission line are reviewed. The analytical relations indicate that the corona current is directly proportional to the square of the corona onset field strength if the ratio of the applied voltage to the corona onset value and that of the conductor height to its radius remain fixed. This is confirmed by numerical results. It is pointed out that this observation makes it possible to derive the basis of a scaled model to evaluate the corona current and hence the resulting power loss of a full-scale unipolar DC line
Keywords :
HVDC power transmission; power cables; power transmission lines; analytical solutions; corona current; corona onset field strength; ionized field; power loss; scaled model; unipolar HVDC transmission line; Coaxial components; Conductors; Corona; Geometry; Guidelines; HVDC transmission; Poisson equations; Power transmission lines; Transmission lines; Voltage;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical Insulation and Dielectric Phenomena, 1999 Annual Report Conference on
Conference_Location :
Austin, TX
Print_ISBN :
0-7803-5414-1
Type :
conf
DOI :
10.1109/CEIDP.1999.804611
Filename :
804611
Link To Document :
بازگشت