• DocumentCode
    3319955
  • Title

    A function of the battery capacity evaluation in telecommunications power systems

  • Author

    Murase, Masatoshi ; Yoshida, Makoto ; Sekiya, Kazuyuki ; Yamashita, Nobiihiko ; Yamashita, Takashi ; Hirai, Toshiro

  • Author_Institution
    NTT Technol. & Dev. Support Center, Chiba, Japan
  • fYear
    1997
  • fDate
    19-23 Oct 1997
  • Firstpage
    592
  • Lastpage
    597
  • Abstract
    This paper describes the evaluation method of VRLA battery deterioration in telecommunications power systems. The rectifier output voltage becomes lower than the rated float voltage of the battery during the test period, which is about 30% of the full-discharge time of the fresh and fully charged battery. Battery discharge time is estimated from the battery discharge voltage characteristics during this period. The degradation rate is determined by comparing the estimated battery discharge time and discharge time of a fresh and fully charged battery. In field tests, the accuracy of estimating battery deterioration was about 20%
  • Keywords
    AC-DC power convertors; lead; rectifying circuits; secondary cells; telecommunication power supplies; Pb; VRLA battery deterioration; battery capacity evaluation; degradation rate; discharge time; discharge voltage characteristics; field tests; rated float voltage; rectifier output voltage; telecommunications power systems; valve-regulated Pb-acid secondary batteries; Battery charge measurement; Circuit testing; Current measurement; Fault location; Power supplies; Power systems; Rectifiers; System testing; Temperature; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Telecommunications Energy Conference, 1997. INTELEC 97., 19th International
  • Conference_Location
    Melbourne, Vic.
  • Print_ISBN
    0-7803-3996-7
  • Type

    conf

  • DOI
    10.1109/INTLEC.1997.646055
  • Filename
    646055