Abstract
This paper describes which factors (i.e. load and supply) have an important effect on the neutral conductor current. It is shown that an asymmetry up to 10° or an unbalance of 10% in the power supply has only a minor effect on the RMS-value of the neutral conductor current. An unbalance in load conditions increases the neutral conductor current. Harmonics in the power supply voltage highly affects the RMS-value of the neutral conductor current
Keywords
load (electric); power system harmonics; RMS-value; load conditions unbalance; neutral conductor current; nonlinear single phase loads; power supply asymmetry; power supply voltage harmonics; three phase supplied network; Conductors; Equations; Fluorescent lamps; Fourier transforms; Intelligent networks; Power supplies; Power system harmonics; Steady-state; Variable speed drives; Voltage;