Abstract
Recently the return voltage measurements have been proposed for the diagnostics on the high voltage equipment characterising the dielectric properties of insulation systems. The application of return voltage method at the diagnostics of the HV current transformers are presented in this paper. The return voltage characteristics such as a maximum of return voltage, the initial slope of return voltage and the time to peak value dependencies on charging time are discussed. These characteristics vary depending on the ageing changes of the insulation. That indicate for a possible applicability of the technique for assessing the state of transformer insulation. The investigations of temperature influence on the return voltage characteristics were aimed to determine the state of the insulation under operating conditions. The theoretical analysis of the results allows to calculate the temperature of insulation that corresponds to the thermal breakdown of insulation
Keywords
ageing; current transformers; insulation testing; power transformer insulation; power transformer testing; voltage measurement; HV current transformer; ageing; dielectric properties; high voltage equipment; insulation diagnostics; return voltage measurement; temperature dependence; thermal breakdown; Current measurement; Current transformers; Dielectrics; Electrical resistance measurement; Oil insulation; Petroleum; Power transformer insulation; Temperature dependence; Time measurement; Voltage measurement;
fLanguage
English
Publisher
ieee
Conference_Titel
Electrical Insulating Materials, 1998. Proceedings of 1998 International Symposium on
Conference_Location
Toyohashi
Print_ISBN
4-88686-050-8
Type
conf
DOI
10.1109/ISEIM.1998.741691
Filename
741691
Link To Document