Title :
Study on Pollution Flashover Characteristics of ±800kV DC Composite Insulators
Author :
Bing, Luo ; Licheng, Li ; Hong, Rao ; Xiaolin, Li
Author_Institution :
Technol. Res. Center, China Southern Power Grid Co. Ltd., Guangzhou
Abstract :
This paper presents the basic structure parameters of 800kV DC composite insulator specimen and the pollution test scheme. The condition of 800kV DC composite insulator pollution test under whole 800kV voltage and whole structure dimension completed in STRI, which is completed first time in the world, is introduced. The study results indicate that the linear relation between the pollution flashover voltage and the length of 800kVDC composite insulator is high-blooded. The consistency of test data between STRI and China lab is good. The pollution flashover characteristics of I string and V string under whole voltage and whole structure dimension is confirmed. The formula of DC pollution flashover grads calculated by SDD of DC composite insulator is obtained.
Keywords :
composite insulators; flashover; insulator contamination; China; DC composite insulators; pollution flashover voltage; pollution test scheme; voltage -800 kV; voltage 800 kV; Africa; Contamination; Design optimization; Flashover; Insulation; Insulator testing; Pollution; Power grids; Power transmission lines; Voltage; UHVDC; composite insulator; flashover characteristics;
Conference_Titel :
Power Engineering Society Conference and Exposition in Africa, 2007. PowerAfrica '07. IEEE
Conference_Location :
Johannesburg
Print_ISBN :
978-1-4244-1477-2
Electronic_ISBN :
978-1-4244-1478-9
DOI :
10.1109/PESAFR.2007.4498056