Wind Turbine Harmonics caused by Unbalanced Grid Currents
Author
Dettmann, Klaus-Dieter ; Schostan, Steffen ; Schulz, Detlef
Author_Institution
Helmut-Schmidt-Univ., Hamburg
fYear
2007
fDate
May 29 2007-June 1 2007
Firstpage
1
Lastpage
6
Abstract
For wind turbines that feed into public grids limits for voltage and current harmonics must be assured. To verify that the actual levels are valid, measurements are necessary. Problems can occur to determine which part of these harmonics has its origin in the wind turbine. It is shown that also harmonics which originally have zero sequences can be transferred over a delta-star-transformer, if the currents of the wind turbine are asymmetric due to unbalanced loads. Measurements in an existing wind turbine configuration are discussed, which confirm the described effects.
Keywords
power grids; power transformers; wind turbines; current harmonics; delta-star-transformer; unbalanced grid current; voltage harmonics; wind turbine harmonics; AC machines; Circuit analysis; Current measurement; Feeds; Harmonic analysis; Phase measurement; Power system harmonics; Power system measurements; Voltage; Wind turbines; AC machines; Circuit analysis; Current measurement; Harmonic analysis; Harmonic distortion; Power system harmonics; Power system measurements; Sequences; Wind energy; Wind power generation;