DocumentCode :
3335295
Title :
Small-disturbance voltage stability of distribution systems with wind turbine implemented with WRIG
Author :
Najafi, H.R. ; Robinson, F.V.P. ; Dastyar, F. ; Samadi, A.A.
Author_Institution :
Univ. of Birjand, Birjand
fYear :
2009
fDate :
18-20 March 2009
Firstpage :
191
Lastpage :
195
Abstract :
The small-disturbance voltage stability of a grid-connected wound-rotor induction-generator (WRIG) wind-turbine system is analyzed under different operating conditions. This theoretical study shows the effect of the wound-rotor induction generator and its parameters on load-bus voltage collapse phenomena. Results show that the rotor resistance of the induction generators may decrease the system voltage stability margin and that the transmission line length has an important effect on the maximum loading point and critical point of loading.
Keywords :
asynchronous generators; power distribution; power system stability; wind turbines; distribution systems; grid-connected wound-rotor induction-generator; load-bus voltage collapse phenomena; small-disturbance voltage stability; wind turbine; Blades; Induction generators; Power generation; Power system modeling; Stability analysis; Voltage; Wind energy; Wind energy generation; Wind speed; Wind turbines;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power Engineering, Energy and Electrical Drives, 2009. POWERENG '09. International Conference on
Conference_Location :
Lisbon
Print_ISBN :
978-1-4244-4611-7
Electronic_ISBN :
978-1-4244-2291-3
Type :
conf
DOI :
10.1109/POWERENG.2009.4915163
Filename :
4915163
Link To Document :
بازگشت