DocumentCode
333833
Title
WSCC testing experience [generating units]
Author
Agrawal, B.L. ; Demcko, J.A.
Author_Institution
Arizona Public Service Co., Phoenix, AZ, USA
Volume
1
fYear
1999
fDate
31 Jan-4 Feb 1999
Firstpage
160
Abstract
This discussion presents some of the practical lessons learned and testing benefits, both expected and unexpected from execution of the WSCC tests. Arizona Public Service Company (APS) has completed testing on over 20 units to date. The units range in size from approximately 40 MVA to over 900 MVA and encompass excitation systems from 1950s vintage amplidynes and magnetic amplifiers to modern solid state static systems. Nearly every unit tested was found to be capable of improved performance with setting modifications or repair of defective elements in the excitation system or governor. Likewise, analysis of the data collected has lead to more accurate computer modeling of several machines tested
Keywords
electric generators; exciters; machine testing; magnetic amplifiers; 40 to 900 MVA; Arizona Public Service Company; WSCC testing experience; amplidynes; computer modeling; defective elements repair; excitation systems; generating units; governor; magnetic amplifiers; setting modifications; solid state static systems; Boosting; Data analysis; Magnetic analysis; Potentiometers; Regulators; Solid state circuits; Switches; System testing; Vibrations; Voltage;
fLanguage
English
Publisher
ieee
Conference_Titel
Power Engineering Society 1999 Winter Meeting, IEEE
Conference_Location
New York, NY
Print_ISBN
0-7803-4893-1
Type
conf
DOI
10.1109/PESW.1999.747443
Filename
747443
Link To Document