Determination of secondary arc extinction time and characterization of fault conditions of single-phase autoreclosures
Author
Luxenburger, Rainer ; Schegner, Peter
Author_Institution
Lab. of Electr. Power Syst. & High Voltage Eng., Technische Univ. Dresden
fYear
2005
fDate
18-18 Nov. 2005
Lastpage
5
Abstract
To classify unsuccessful single-phase autoreclosures, in this paper fault records of successful and unsuccessful single-phase autoreclosures in a German transmission network are investigated. In order to analyze the fault records, a new method is developed to determine the time of secondary arc extinction. An extended method to distinguish between arc faults and others is also presented. Both methods are based on analyzes of the waveform and the spectrum of the faulty line voltage after the opening of the faulted phase
Keywords
arcs (electric); fault diagnosis; power transmission faults; power transmission protection; German transmission network; arc extinction; arc faults; fault conditions; fault records; faulty line voltage; secondary arc; single-phase autoreclosures; Discrete Fourier transforms; Earth; Electric breakdown; Fault location; Inspection; Laboratories; Power harmonic filters; Power system harmonics; Protection; Voltage; EHV transmission lines; characterization of faults; distance protection; fault records; secondary arc; single phase autoreclosures;