DocumentCode :
3339384
Title :
Transient response of doubly fed induction generator under voltage sag using an accurate model
Author :
Abbaszadeh, Alireza ; Lesan, Saeed ; Mortezapour, Vahid
Author_Institution :
Dept. of Electr. Eng., Noshirvani Univ., Babol, Iran
fYear :
2009
fDate :
28-30 Sept. 2009
Firstpage :
1
Lastpage :
6
Abstract :
In order to investigate the transient response of doubly fed induction generator (DFIG) under grid disturbances, an accurate model is required. In this paper transient response of DFIG during voltage sag considering saturation effect of leakage flux for different order models is simulated. It´s shown that if the saturation effect is neglected, simulation result display less current than real one. Then, rotor over-current due to voltage sag and factors that affect it is investigated using saturated model.
Keywords :
asynchronous generators; fault diagnosis; power supply quality; transient response; doubly fed induction generator; grid disturbances; leakage flux; saturated model; transient response; voltage sag; Electronic mail; Equations; Induction generators; Rotors; Stators; Transient response; Voltage fluctuations; Wind energy generation; Wind farms; Wind turbines; Doubly Fed Induction Generator; Modeling; Saturation; Transient Response; Voltage Sag;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Sustainable Alternative Energy (SAE), 2009 IEEE PES/IAS Conference on
Conference_Location :
Valencia
Print_ISBN :
978-1-4244-4430-4
Electronic_ISBN :
978-1-4244-4431-1
Type :
conf
DOI :
10.1109/SAE.2009.5534834
Filename :
5534834
Link To Document :
بازگشت