• DocumentCode
    3344358
  • Title

    Wavelet packet analysis of the applied voltage waveform as a monitoring technique of the outdoor insulation surface

  • Author

    Moula, B. ; Mekhaldi, A. ; Teguar, M.

  • Author_Institution
    Dept. de Genie Electr., Ecole Nat. Polytech. d´Alger (ENP), Alger, Algeria
  • fYear
    2013
  • fDate
    June 30 2013-July 4 2013
  • Firstpage
    174
  • Lastpage
    177
  • Abstract
    The objective of our study is to analyse the ac applied voltage signals recorded for different pollution levels using a following technique: wavelet packet analysis. Laboratory tests were performed on flat plate models of glass (500×500×5 mm) under uniform pollution. The plate models were sprayed with a solution prepared by mixing 100 g of kaolin in one liter of distilled water. An appropriate amount of NaCl was added to the slurry to give required Equivalent Salt Deposit Density (ESDD). The various studied ESDD are as follows: 1.2, 3.5, 6, 10, 15 and 20 mS/cm. The obtained results show that this technique constitutes a very effective tool to estimate the pollution severity degree on outdoor insulation surface.
  • Keywords
    flashover; glass; slurries; surface contamination; ESDD; ac applied voltage waveform signal; distilled water; equivalent salt deposit density; flat plate model; glass; kaolin; outdoor insulation surface monitoring; pollution severity; slurry; wavelet packet analysis; Conductivity; Insulation; Leakage currents; Pollution; Surface contamination; Wavelet analysis; Wavelet packets; Outdoor insulation surface; applied voltage; pollution severity; wavelet packet;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Solid Dielectrics (ICSD), 2013 IEEE International Conference on
  • Conference_Location
    Bologna
  • ISSN
    2159-1687
  • Print_ISBN
    978-1-4799-0807-3
  • Type

    conf

  • DOI
    10.1109/ICSD.2013.6619893
  • Filename
    6619893