Abstract :
Anti-islanding protection and maximum power point tracking for a two stage photovoltaic grid-connected inverter is designed in this paper. A new algorithm based on the traditional active frequency drift method is proposed to decrease none detection zone of the islanding detection. Perturbation and Observation method is adopted for the maximum power point tracking of the boost converter of the input stage. The stored energy in the filter capacitor changes under the voltage perturbation and it decreases the precision of MPPT. With stored energy change feed forward control, the precision of the MPPT method is improved.
Keywords :
invertors; photovoltaic power systems; power convertors; power generation protection; power grids; active frequency drift method; anti-islanding protection; boost converter; feed forward control; filter capacitor; maximum power point tracking; observation method; photovoltaic grid-connected inverter; Capacitors; Control systems; Feeds; Filters; Frequency; Inductors; Protection; Pulse width modulation inverters; Switches; Voltage control;