DocumentCode
3350474
Title
Application of DSTATCOM for Mitigation of Voltage Sag for Motor Loads in Isolated Distribution Systems
Author
Singh, Bhim ; Adya, A. ; Mittal, A.P. ; Gupta, J.R.P. ; Singh, B.N.
Author_Institution
Dept. of Electr. Eng., Indian Inst. of Technol., New Delhi
Volume
3
fYear
2006
fDate
9-13 July 2006
Firstpage
1806
Lastpage
1811
Abstract
This paper deals with one of the potential applications of distribution static compensator (DSTATCOM) to industrial systems for mitigation of voltage dip problem. The dip in voltage is generally encountered during the starting of an induction motor. Isolated distribution systems are comparatively not as stiff as grid systems; so large starting currents and objectionable voltage drop during starting of an induction motor could be critical for the entire system. DSTATCOM is one effective solution for isolated power systems facing such power quality problems. The model of DSTATCOM connected in shunt configuration to such an isolated system (3phase, 42.5 kVA alternator) feeding dynamic motor loads is developed using Simulink and PSB of MATLAB software. Simulated results demonstrate that DSTATCOM can be a considered as a viable solution for solving such voltage dip problems
Keywords
distribution networks; induction motors; power supply quality; static VAr compensators; DSTATCOM; distribution static compensator; induction motor starting; isolated distribution systems; power quality problems; voltage dip problem mitigation; voltage sag mitigation; Alternators; Induction motors; MATLAB; Mathematical model; Power quality; Power system dynamics; Power system modeling; Power system simulation; STATCOM; Voltage fluctuations; DSTATCOM; induction motor; voltage regulation;
fLanguage
English
Publisher
ieee
Conference_Titel
Industrial Electronics, 2006 IEEE International Symposium on
Conference_Location
Montreal, Que.
Print_ISBN
1-4244-0496-7
Electronic_ISBN
1-4244-0497-5
Type
conf
DOI
10.1109/ISIE.2006.295846
Filename
4078521
Link To Document