Abstract
In order to know discharge type exactly, contamination discharge AE and corona AE of insulator are compared by experiments. Increase test voltage and vary work condition, at the same time, measure and record AE wave from contamination discharge and corona discharge, then the varying laws of AE with test voltage and with test time during the two discharges are analyzed and compared. Experiment result shows that corona discharge AE and contamination discharge AE can be both detected by AE sensor, and they appear both in periodicity and in axial symmetry in test voltage period. However, there are some obvious differences in the two discharges, such as AE event count in a test period, AE start voltage, test voltage stability, test time stability and AE´s shape. So applying the differences to identify the discharge type of insulator should be effective and feasible.
Keywords
corona; insulators; AE start voltage; axial symmetry; contamination discharge AE; corona discharge AE; insulator discharge; test time stability; test voltage stability; Circuit faults; Coils; Contamination; Corona; Oscilloscopes; Pollution measurement; Power transformer insulation; Stability; Testing; Voltage;
fLanguage
English
Publisher
ieee
Conference_Titel
Power and Energy Engineering Conference, 2009. APPEEC 2009. Asia-Pacific
Conference_Location
Wuhan
Print_ISBN
978-1-4244-2486-3
Electronic_ISBN
978-1-4244-2487-0
Type
conf
DOI
10.1109/APPEEC.2009.4918225
Filename
4918225
Link To Document