DocumentCode
3353511
Title
Research on return voltage method to diagnose insulation moisture in transformer
Author
Xiu-bo, Jiang ; Tao, Zhang
Author_Institution
Coll. of Electr. Eng. & Autom., Fuzhou Univ., Fuzhou, China
fYear
2010
fDate
26-28 June 2010
Firstpage
4042
Lastpage
4045
Abstract
Moisture in power transformer strongly influences the dielectric properties of oil-paper insulation system. The insulation paper gradually degrades over time, therefore, it is imperative to assess integral condition of oil-paper insulation for assuring a normal operation of power transformers. As a non-destructive diagnostic technique, return voltage measurement is an effective assessment method of water content in transformer pressboard. The study presented in this paper aims of further investigating the reliability of the quantification of water content using dominant time constant in transformer pressboard. Field tests performed on several transformers in different status have shown that the return voltage measurement method can estimate the moisture content in paper insulation of power transformers effectively.
Keywords
dielectric properties; paper; power transformer insulation; transformer oil; dielectric properties; insulation moisture diagnosis; nondestructive diagnostic technique; oil-paper insulation system; power transformer; return voltage measurement method; return voltage method; transformer pressboard; water content; Aging; Circuit testing; Dielectrics and electrical insulation; Moisture; Oil insulation; Power transformer insulation; Power transformers; Solids; Switches; Voltage; Dielectric Properties; Insulation moisture; Return voltage method; Transformer;
fLanguage
English
Publisher
ieee
Conference_Titel
Mechanic Automation and Control Engineering (MACE), 2010 International Conference on
Conference_Location
Wuhan
Print_ISBN
978-1-4244-7737-1
Type
conf
DOI
10.1109/MACE.2010.5535895