DocumentCode :
3358049
Title :
Analysis of transient currents of the connected self- excited induction generator following disturbance on the system supply
Author :
Mekhtoub, S. ; Ibtiouen, R. ; Touhami, O. ; Bacha, S.
Author_Institution :
Nat. Sch. Polytech. Algiers, Algiers
fYear :
2007
fDate :
10-12 Sept. 2007
Firstpage :
696
Lastpage :
700
Abstract :
In this paper, the analysis of self excited induction generator (SEIG) connected to utility grid is studied. We simulated the reconnection of the SIEG to the utility grid after a short perturbation. A mathematical model of the induction generator using Park´s model, where taking account the saturation of the magnetizing flux is developed. The experimental results of transient currents are approached by simulation, because the initial conditions are not the same ones in practice.
Keywords :
asynchronous generators; mathematical analysis; power grids; transient analysis; Parks model; grid connection; magnetizing flux; mathematical model; self-excited induction generator; transient currents analysis; Educational institutions; Equations; Induction generators; Leg; Magnetic flux; Mathematical model; Saturation magnetization; Space stations; Switches; Transient analysis; Induction generator; Modelling; grid connection; self-excitation;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical Machines and Power Electronics, 2007. ACEMP '07. International Aegean Conference on
Conference_Location :
Bodrum
Print_ISBN :
978-1-4244-0890-0
Electronic_ISBN :
978-1-4244-0891-7
Type :
conf
DOI :
10.1109/ACEMP.2007.4510592
Filename :
4510592
Link To Document :