Title :
Research on the Over-Voltage of 220kV Power System Caused by Traction Transformer´s Commissioning
Author :
Ma Weiping ; Cheng Fangxiao ; Zhou Wenjun
Author_Institution :
Dept. of High Voltage, Jilin Electr. Power Res. Inst., Changchun
Abstract :
The over-voltage of 220 kV power system appeared during the commissioning of several traction transformers in Jilin Province. Analysis showed that the electromagnetic oscillating of the system caused the over-voltage of the feeding phases. After setting up an accurate simulating model used in ATP-EMTP, the adverse influence on the electric power system and the character of the oscillation over-voltage had been studied. Results showed that under the environment of these substations the amplitude of the over-voltage couldn´t exceed 2.0 p.u and would have little influence on electric power system.
Keywords :
commissioning; oscillations; overvoltage; power transformers; traction; ATP-EMTP simulation; Jilin Province; electric power system; electromagnetic oscillation; overvoltage; traction transformer commissioning; voltage 220 kV; Equivalent circuits; Frequency; Phase transformers; Power system modeling; Power system simulation; Power systems; Power transmission lines; Rail transportation; Substations; System testing;
Conference_Titel :
Power and Energy Engineering Conference, 2009. APPEEC 2009. Asia-Pacific
Conference_Location :
Wuhan
Print_ISBN :
978-1-4244-2486-3
Electronic_ISBN :
978-1-4244-2487-0
DOI :
10.1109/APPEEC.2009.4918719