• DocumentCode
    3359998
  • Title

    Reliability of electronic ballasts in industrial fluorescent lighting applications

  • Author

    Biswas, Sujit K., Sr. ; Dhanuka, R.P.

  • Author_Institution
    Dept. of Electr. Eng., Jadavpur Univ., Calcutta, India
  • fYear
    1992
  • fDate
    4-9 Oct. 1992
  • Firstpage
    1915
  • Abstract
    The premature failure of electronic ballasts installed in industrial sites was investigated. The objective was to locate the specific causes so that manufacturers can redesign the ballasts for higher reliability. Conditions of the site where the ballasts were installed and the types of components that failed were examined. The main reasons for failure were abnormal voltage rises, both steady and transient in nature. Based on the analysis, suitable modifications were made to the component rating, selection, and test procedures so that reliability could be increased. Fresh data collected from the same sites using the modified ballasts showed greatly reduced mortality.<>
  • Keywords
    failure analysis; fluorescent lamps; lamp accessories; reliability; abnormal voltage rises; electronic ballasts; failure; industrial fluorescent lighting applications; reliability; steady state; transient; Circuits; Electricity supply industry; Electronic ballasts; Electronics industry; Energy consumption; Fluorescence; Fluorescent lamps; Frequency; Inductors; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Industry Applications Society Annual Meeting, 1992., Conference Record of the 1992 IEEE
  • Conference_Location
    Houston, TX, USA
  • Print_ISBN
    0-7803-0635-X
  • Type

    conf

  • DOI
    10.1109/IAS.1992.244218
  • Filename