• DocumentCode
    336040
  • Title

    Partial discharge measurements in distribution class extruded cables

  • Author

    Ahmed, Nezar ; Srinivas, Nagu

  • Author_Institution
    Detroit Univ., MI, USA
  • Volume
    1
  • fYear
    1999
  • fDate
    11-16 Apr 1999
  • Firstpage
    46
  • Abstract
    Several distribution-class extruded-cables subjected to laboratory-accelerated aging were examined for partial discharges (PD). The cables were subjected to different load cycling while fully immersed in water to obtain different aging conditions. PD initiated in these cables was measured at rated and at elevated voltages. Correlation between the PD-signature and the insulation-defects type was examined. This was achieved by comparing the PD frequency, magnitude and phase angles of different insulation defects. Correlation between the PD level and AC breakdown voltage of these cables also is presented in this paper. The same investigations also were repeated on several cables removed from service after 15-20 years of service. Correlation between the PD levels and the cable remaining life also was investigated
  • Keywords
    ageing; distribution networks; insulation testing; life testing; partial discharge measurement; power cable insulation; power cable testing; AC breakdown voltage; aging conditions; distribution class extruded cables; insulation defects; laboratory-accelerated aging; load cycling; partial discharge measurements; power cable insulation testing; remaining life; Aging; Cable insulation; Condition monitoring; Frequency domain analysis; Partial discharge measurement; Partial discharges; Pulse measurements; Reflection; Testing; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Transmission and Distribution Conference, 1999 IEEE
  • Conference_Location
    New Orleans, LA
  • Print_ISBN
    0-7803-5515-6
  • Type

    conf

  • DOI
    10.1109/TDC.1999.755314
  • Filename
    755314