• DocumentCode
    3362963
  • Title

    On-site testing for mobile particles in GIS under impulse voltages

  • Author

    Anis, H. ; Ward, Sayed A.

  • Author_Institution
    Cairo Univ., Egypt
  • fYear
    1992
  • fDate
    4-9 Oct 1992
  • Firstpage
    1487
  • Abstract
    The work models the performance of mobile particles in compressed-gas-insulated substations under an intentionally applied impulse voltage of reduced magnitude. The subsequent microdischarges are used to detect the presence of particles and identify their approximate sizes. A comprehensive computer model is described. It describes and interrelates the potential and field distributions on and around the particle, particle lifting and movement, timing of the initial microdischarge, and the complete pattern of the microdischarges as might be detected by an external monitoring circuit
  • Keywords
    charge measurement; gaseous insulation; impulse testing; partial discharges; power engineering computing; substations; compressed-gas-insulated substations; computer model; external monitoring circuit; impulse voltage; microdischarges; mobile particles; particle lifting; Coaxial components; Computerized monitoring; Equations; Geographic Information Systems; Impulse testing; Ionization; Partial discharges; Timing; Voltage; Wire;