DocumentCode
3362963
Title
On-site testing for mobile particles in GIS under impulse voltages
Author
Anis, H. ; Ward, Sayed A.
Author_Institution
Cairo Univ., Egypt
fYear
1992
fDate
4-9 Oct 1992
Firstpage
1487
Abstract
The work models the performance of mobile particles in compressed-gas-insulated substations under an intentionally applied impulse voltage of reduced magnitude. The subsequent microdischarges are used to detect the presence of particles and identify their approximate sizes. A comprehensive computer model is described. It describes and interrelates the potential and field distributions on and around the particle, particle lifting and movement, timing of the initial microdischarge, and the complete pattern of the microdischarges as might be detected by an external monitoring circuit
Keywords
charge measurement; gaseous insulation; impulse testing; partial discharges; power engineering computing; substations; compressed-gas-insulated substations; computer model; external monitoring circuit; impulse voltage; microdischarges; mobile particles; particle lifting; Coaxial components; Computerized monitoring; Equations; Geographic Information Systems; Impulse testing; Ionization; Partial discharges; Timing; Voltage; Wire;
fLanguage
English
Publisher
ieee
Conference_Titel
Industry Applications Society Annual Meeting, 1992., Conference Record of the 1992 IEEE
Conference_Location
Houston, TX
Print_ISBN
0-7803-0635-X
Type
conf
DOI
10.1109/IAS.1992.244391
Filename
244391
Link To Document