DocumentCode
3364934
Title
Health diagnostics of water-cooled power generator stator windings using a Directional Mahalanobis Distance (DMD)
Author
Kyung Min Park ; Youn, Byeng D. ; Joung Taek Yoon ; Chao Hu ; Hee Soo Kim ; Yong Chae Bae
Author_Institution
Sch. of Mech. & Aerosp. Eng., Seoul Nat. Univ., Seoul, South Korea
fYear
2013
fDate
24-27 June 2013
Firstpage
1
Lastpage
8
Abstract
A power generator, one of the most critical components in power plant, could experience unexpected series system failures, resulting in substantial maintenance and societal cost. This paper proposes a new health diagnostics method for water-cooled power generator windings against moisture absorption. The main idea of the proposed diagnostics method is a Directional Mahalanobis Distance (DMD) based on the correlation matrix of health data. In this study capacitance data measured from a winding insulator is referred to as health data. It is an indirect measure of moisture absorption in power generator windings by water leakage. Data from ten generators, of which each has 42 windings, are used for demonstration of the proposed health diagnostics method for power generator windings.
Keywords
electric generators; matrix algebra; statistical analysis; stators; DMD; capacitance data; directional Mahalanobis distance; health data correlation matrix; health diagnostics method; moisture absorption; water leakage; water-cooled power generator stator windings; winding insulator; Absorption; Correlation; Equations; Windings; Directional Mahalanobis Distance; Health Diagnostics; Moisture Absorption; Power Generator Stator Winding; Statistical Correlation;
fLanguage
English
Publisher
ieee
Conference_Titel
Prognostics and Health Management (PHM), 2013 IEEE Conference on
Conference_Location
Gaithersburg, MD
Print_ISBN
978-1-4673-5722-7
Type
conf
DOI
10.1109/ICPHM.2013.6621439
Filename
6621439