    Health diagnostics of water-cooled power generator stator windings using a Directional Mahalanobis Distance (DMD)

  • Author

    Kyung Min Park ; Youn, Byeng D. ; Joung Taek Yoon ; Chao Hu ; Hee Soo Kim ; Yong Chae Bae

  • Author_Institution
    Sch. of Mech. & Aerosp. Eng., Seoul Nat. Univ., Seoul, South Korea
  • fYear
    2013
  • fDate
    24-27 June 2013
  • Firstpage
    1
  • Lastpage
    8
  • Abstract
    A power generator, one of the most critical components in power plant, could experience unexpected series system failures, resulting in substantial maintenance and societal cost. This paper proposes a new health diagnostics method for water-cooled power generator windings against moisture absorption. The main idea of the proposed diagnostics method is a Directional Mahalanobis Distance (DMD) based on the correlation matrix of health data. In this study capacitance data measured from a winding insulator is referred to as health data. It is an indirect measure of moisture absorption in power generator windings by water leakage. Data from ten generators, of which each has 42 windings, are used for demonstration of the proposed health diagnostics method for power generator windings.
  • Keywords
    electric generators; matrix algebra; statistical analysis; stators; DMD; capacitance data; directional Mahalanobis distance; health data correlation matrix; health diagnostics method; moisture absorption; water leakage; water-cooled power generator stator windings; winding insulator; Absorption; Correlation; Equations; Windings; Directional Mahalanobis Distance; Health Diagnostics; Moisture Absorption; Power Generator Stator Winding; Statistical Correlation;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Prognostics and Health Management (PHM), 2013 IEEE Conference on
  • Conference_Location
    Gaithersburg, MD
  • Print_ISBN
    978-1-4673-5722-7
  • Type

    conf

  • DOI
    10.1109/ICPHM.2013.6621439
  • Filename
    6621439