DocumentCode :
3367305
Title :
On-line monitoring of electrodynamic effects on power transformers windings
Author :
Arri, E. ; Mocci, F. ; Tosi, M.
Author_Institution :
Politecnico di Torino, Italy
fYear :
1992
fDate :
12-14 May 1992
Firstpage :
466
Lastpage :
469
Abstract :
A strategy for protecting power transformers, based on the possibility of taking measurements on machines under real operating conditions, is discussed. A measurement technique for determining the online variations of stray reactance of transformers due to short-circuit events is reported. This parameter can be indicative of winding geometry; hence it makes possible the setting up a diagnostic system that provides useful indications of conductor insulation reliability. This method is suitable, with the proper choice of measuring device constants, not only for identifying core and winding losses, but also for determining the changes of short-circuit reactance of the transformer
Keywords :
automatic test equipment; computerised monitoring; loss measurement; power transformers; short-circuit currents; transformer protection; transformer testing; transformer windings; conductor insulation reliability; core losses; diagnostic system; electrodynamic effects; online monitoring; online variations; power transformers windings; short-circuit events; short-circuit reactance; stray reactance; winding geometry; winding losses; Conductors; Electrodynamics; Geometry; Loss measurement; Measurement techniques; Monitoring; Power measurement; Power transformer insulation; Power transformers; Protection;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Instrumentation and Measurement Technology Conference, 1992. IMTC '92., 9th IEEE
Conference_Location :
Metropolitan, NY
Print_ISBN :
0-7803-0640-6
Type :
conf
DOI :
10.1109/IMTC.1992.245095
Filename :
245095
Link To Document :
بازگشت