Testing numerical transformer differential relays
Author
Turner, Steve
Author_Institution
Beckwith Electr. Co. Inc., Largo, FL
fYear
2009
fDate
26-29 April 2009
Abstract
Numerical transformer differential relays require careful consideration regarding how to test them properly. These relays provide different types of protection such as restrained phase differential, high set phase differential, restrained ground differential and overcurrent protection. All protection elements that are enabled should be adequately tested. A common commissioning practice is to test all the numerical relay settings to verify they were properly entered. Automated testing using computer software to run the test set has made this possible since the overall commissioning for a numerical relay could consist of several hundred tests. While this is a good check, it is still important to ensure that the transformer is thoroughly protected for the particular application.
Keywords
overcurrent protection; power system harmonics; power transformer protection; power transformer testing; relay protection; ground differential; harmonic restraint; overcurrent protection; phase differential; transformer differential relays; transformer inrush; transformer protection; Application software; Automatic testing; Differential equations; Integrated circuit testing; Protection; Protective relaying; Relays; Software testing; Surges; Windings; Transformer protection; even harmonic restraint; ground differential; overcurrent protection; transformer differential relay; transformer inrush;
fLanguage
English
Publisher
ieee
Conference_Titel
Rural Electric Power Conference, 2009. REPC '09. IEEE
Conference_Location
Fort Collins, CO
Print_ISBN
978-1-4244-3420-6
Electronic_ISBN
978-1-4244-4301-7
Type
conf
DOI
10.1109/REPCON.2009.4919424
Filename
4919424
Link To Document