DocumentCode :
3368063
Title :
Uprating using high-temperature electrical conductors [overhead power lines]
Author :
Zamora, I. ; Mazón, A.J. ; Criado, R. ; Alonso, C. ; Saenz, J.R.
Author_Institution :
Basque Country Univ., Spain
Volume :
1
fYear :
2001
fDate :
2001
Abstract :
This paper presents the most important results of the COALPRET research project, whose dual aim has been to carry out a general study of the characteristics of electrical conductors with high temperature performance and low sag, and apply these studies to the specific case of Spain´s Alcira-Gandia 132 kV overhead transmission line. The final goal of the project is the replacement, in the Alcira-Gandia line, of the current ACSR conductors by another type of conductor with low sag characteristics. With this replacement, the aim is to increase the ampacity rating of the aforementioned line by at least 70%, with the smallest increase in sag, as there are currently numerous spans where the distances of line to earth are very compromising
Keywords :
maintenance engineering; overhead line conductors; overhead line mechanical characteristics; power overhead lines; project engineering; thermal analysis; 132 kV; COALPRET research project; Spain; ampacity rating; high temperature performance; high-temperature electrical conductors; low sag characteristics; overhead transmission line uprating;
fLanguage :
English
Publisher :
iet
Conference_Titel :
Electricity Distribution, 2001. Part 1: Contributions. CIRED. 16th International Conference and Exhibition on (IEE Conf. Publ No. 482)
Conference_Location :
Amsterdam
ISSN :
0537-9989
Print_ISBN :
0-85296-735-7
Type :
conf
DOI :
10.1049/cp:20010687
Filename :
942787
Link To Document :