• DocumentCode
    3370127
  • Title

    Reliability study for the refurbishment of a HV/MV transformer substation

  • Author

    Osterholt, A. ; Prause, U. ; Zimmermann, W.

  • Author_Institution
    ABB Calor Emag Schaltanlagen AG, Germany
  • Volume
    3
  • fYear
    2001
  • fDate
    2001
  • Abstract
    In the main HV/MV substation of a German distribution utility, its refurbishment is upcoming. It was the objective of the presented study, to find the economic and technical optimal solution for the medium-voltage (MV) busbar-arrangement from a functional point of view. In addition to the existing configuration (double-busbar-arrangement), simplified alternatives (single-busbar- and ring-busbar-arrangement) were designed and studied by means of probabilistic reliability calculation. The results show clearly, that the simplified configurations are almost equal with regard to the provided supply reliability and also under operational aspects they cause no essential restriction. Consequently the higher investment cost of a double-busbar-arrangement cannot be justified
  • Keywords
    busbars; maintenance engineering; power system reliability; probability; transformer substations; Germany; HV/MV transformer substation refurbishment; busbar-arrangement; distribution utility; double-busbar-arrangement; investment cost; optimal solution; probabilistic reliability calculation; reliability study; ring-busbar-arrangement; single-busbar-arrangement;
  • fLanguage
    English
  • Publisher
    iet
  • Conference_Titel
    Electricity Distribution, 2001. Part 1: Contributions. CIRED. 16th International Conference and Exhibition on (IEE Conf. Publ No. 482)
  • Conference_Location
    Amsterdam
  • ISSN
    0537-9989
  • Print_ISBN
    0-85296-735-7
  • Type

    conf

  • DOI
    10.1049/cp:20010799
  • Filename
    942941