DocumentCode :
337566
Title :
Harmonic monitoring system via synchronized measurements
Author :
Fardanesh, Bruce ; Zelingher, Shalom ; MelioPoulos, A. P Sakis ; Cokkinides, George J.
Author_Institution :
New York Power Authority, New York, NY, USA
Volume :
1
fYear :
1998
fDate :
14-18 Oct 1998
Firstpage :
482
Abstract :
The New York Power Authority (NYPA), and the other Empire State Electric Energy Research Corporation (ESEERCO) member utilities, initiated deployment of a high voltage transmission harmonic measurement system (HMS) in 1992. The HMS consists of hardware and software, which determine the harmonic state of a transmission system, in real time, and stores the acquired data in a historical harmonic database. The HMS hardware consists of GPS synchronized digital event recorders linked to on-site computers, and a master station computer. The present installation includes instrumentation for a total of 150 measurements of which 138 are three phase quantities (voltages or currents) resulting in 46 phasors. The system performs synchronized waveform data acquisition every 15 minutes. The captured data are processed at the on-site computers to correct for error from the nonideal characteristics of the instrumentation, and to compute the harmonics. The computed harmonics (magnitude and phase) are transmitted to the master station computer where the system wide harmonic flow is constructed, using a harmonic state estimation technique. This paper describes the HMS hardware and software as well as HMS applications
Keywords :
Global Positioning System; computerised monitoring; data acquisition; database management systems; power system analysis computing; power system harmonics; power system measurement; power system state estimation; real-time systems; synchronisation; Empire State Electric Energy Research Corporation; GPS synchronized digital event recorders; New York Power Authority; computed harmonics; harmonic monitoring system; harmonic state estimation technique; high voltage transmission harmonic measurement system; historical harmonic database; master station computer; on-site computers; real time; synchronized measurements; synchronized waveform data acquisition; system wide harmonic flow; three phase quantities; transmission system harmonic state; Databases; Electric variables measurement; Energy measurement; Hardware; Instruments; Monitoring; Power measurement; Power system harmonics; Real time systems; Voltage measurement;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Harmonics and Quality of Power Proceedings, 1998. Proceedings. 8th International Conference On
Conference_Location :
Athens
Print_ISBN :
0-7803-5105-3
Type :
conf
DOI :
10.1109/ICHQP.1998.759956
Filename :
759956
Link To Document :
بازگشت