Title :
Coherence function method of detection of fault in a power transformer during impulse test
Author :
Reddy, K. Shashidhar ; Kumar, M.P.V.V.R. ; Singh, B.P. ; Suryakalavathi, M.
Author_Institution :
St. Martin´´s Eng. Coll., Secunderabad, India
Abstract :
The paper discusses the coherence function method of fault detection in a power transformer during impulse test. It is based on calculation of neutral current in a transformer on the basis of derived equivalent electrical network of the winding. Turn faults are theoretically simulated in the high voltage coil of 220 KV, 100 MVA winding. The neutral current and its Fourier Transform are calculated for simulated HV coil without and with turn fault. The output of frequency response is subjected to coherence function calculation. The results indicate a higher sensitivity of detection of fault with coherence function compared to that of frequency response. A method to calibrate various types of noise superimposed on impulse voltage is also discussed with a view to explain coherence results obtained above.
Keywords :
Fourier transforms; coils; fault diagnosis; frequency response; impulse testing; power transformer testing; transformer windings; Fourier transform; apparent power 100 MVA; coherence function method; equivalent electrical network; fault detection; frequency response; high voltage coil; impulse test; impulse voltage; neutral current; power transformer winding; simulated HV coil; voltage 220 kV; Calibration; Circuit faults; Coherence; Frequency response; Noise; Power transformers; Windings;
Conference_Titel :
Power and Energy Systems (ICPS), 2011 International Conference on
Conference_Location :
Chennai
Print_ISBN :
INAVLID ISBN
DOI :
10.1109/ICPES.2011.6156635