DocumentCode :
33772
Title :
Partial discharge diagnostics for mixed-technology switchgear (MTS) in outdoor substations
Author :
Lopez-Roldan, Jose ; Blundell, M. ; Irwin, T. ; Charlson, C.
Author_Institution :
Powerlink Queensland, Virginia, QLD, Australia
Volume :
29
Issue :
3
fYear :
2013
fDate :
May-June 2013
Firstpage :
41
Lastpage :
47
Abstract :
The application of the UHF method to PD measurements in MTS substations presents technical challenges due to the much higher external noise in outdoor substations. To adapt the UHF technique to handle these challenges, a series of tests was performed in the laboratory and at selected substations. Different PD sources were inserted in a test rig, and the proposed UHF detection system was evaluated. On-site measurements using this system showed that the spectra of external and internal PD sources differed considerably, suggesting that the system is capable of yielding reliable indications of the presence of PD in MTS.
Keywords :
partial discharge measurement; substations; switchgear; MTS substations; PD measurements; PD sources; UHF detection system; UHF technique; external noise; mixed-technology switchgear; on-site measurements; outdoor substations; partial discharge diagnostics; partial discharge measurements; Detectors; Frequency response; Gas insulation; Partial discharges; Substations; Switchgear; GIS; detector; gas-insulated switchgear; hybrid switchgear; mixed-technology switchgear; outdoor substation; partial discharge; ultra-high frequency;
fLanguage :
English
Journal_Title :
Electrical Insulation Magazine, IEEE
Publisher :
ieee
ISSN :
0883-7554
Type :
jour
DOI :
10.1109/MEI.2013.6507413
Filename :
6507413
Link To Document :
بازگشت