DocumentCode
3381240
Title
The Performance of Faulted Phase Selectors Used in Transmission Line Distance Applications
Author
Price, Elmo ; Einarsson, Torbjorn
Author_Institution
ABB Inc., Norwalk, CT
fYear
2008
fDate
1-3 April 2008
Firstpage
484
Lastpage
490
Abstract
The reliable performance of faulted phase selectors to identify the faulted phase or phases and appropriately block or permit tripping is critical to the application of distance protection. The most difficult fault type to identify correctly is a two-phase-to-ground fault. Incorrect detection methods of this fault type has lead to undesired overreaching and/or tripping for remote two-phase-to-ground faults beyond the underreaching zone reach setting. It is also important to provide accurate fault location and record correct faulted phase information after the fault has cleared to correctly access the fault type characteristics. This paper analyzes the issues related to two-phase-to-ground faults and discusses several methods used for faulted phase identification and the advantages and disadvantages of each. It also shows how different phase selection methods may be used to complement each other to provide more reliable faulted phase identification.
Keywords
earthing; fault diagnosis; power system protection; relay protection; transmission lines; distance protection; faulted phase selectors; permit tripping; protective relaying; transmission line distance applications; two-phase-to-ground fault; Character generation; Current measurement; Electrical resistance measurement; Fault diagnosis; Fault location; Impedance measurement; Measurement units; Phase measurement; Protection; Transmission lines; Distance measurement; Protective relaying; phase selection;
fLanguage
English
Publisher
ieee
Conference_Titel
Protective Relay Engineers, 2008 61st Annual Conference for
Conference_Location
College Station, TX
Print_ISBN
978-1-4244-1949-4
Type
conf
DOI
10.1109/CPRE.2008.4515074
Filename
4515074
Link To Document