    Measurements of transient grounding impedance of a wind turbine at the Mont-Crosin wind park

  • Author

    Smorgonskiy, Alexander ; Mora, Nicolas ; Raclndi, Farhad ; Rubinstein, Marcos ; Sheshyekani, Keyhan ; Korovkin, Nikolay

  • Author_Institution
    EMC Lab., Ecole Polytech. federate de Lausanne, Lausanne, Switzerland
  • fYear
    2015
  • fDate
    26-29 May 2015
  • Firstpage
    424
  • Lastpage
    427
  • Abstract
    In this paper, we report the results of wind turbine grounding system impedance measurements performed at the Mont-Crosin wind park in Switzerland. Experiments were carried out twice: (1) when only the construction of the wind turbine foundation had been completed, and (2) once the installation of the rest of the wind turbine was finished: tower, nacelle and blades. The transient grounding impedance was evaluated directly in the time domain by solving Duhamel´s integral equation. The influence of the presence of the wind turbine is found to be negligible on the grounding impedance at low frequencies. However, at frequencies beyond 150 kHz or so, the measurement of the grounding impedance is significantly affected by the presence of the wind turbine.
  • Keywords
    earthing; electric impedance measurement; integral equations; time-domain analysis; wind turbines; Duhamel integral equation; Mont-Crosin wind park; Switzerland; blade; nacelle; time domain; tower; wind turbine foundation construction; wind turbine installation; wind turbine transient grounding system impedance measurement; Impedance; Impedance measurement; Poles and towers; Soil; Soil measurements; Transient analysis;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electromagnetic Compatibility (APEMC), 2015 Asia-Pacific Symposium on
  • Conference_Location
    Taipei
  • Print_ISBN
    978-1-4799-6668-4
  • Type

    conf

  • DOI
    10.1109/APEMC.2015.7175376
  • Filename
    7175376