DocumentCode
3384603
Title
Improved Detection Method of Current Component Based on Instantaneous Reactive Power Theory
Author
Ma Wenchuan ; Zhang Shuo ; Wang Shuwen ; Song Yuzhu ; Dongmei Zhang ; Gang Han
Author_Institution
Dept. of Electr. Eng., Northeast Agric. Univ., Harbin, China
fYear
2012
fDate
27-29 March 2012
Firstpage
1
Lastpage
4
Abstract
Due to ip-iq current detection method based on instantaneous reactive power theory will produce detecting error when voltage is unbalance, This paper proposed a method which uses the phase angle of positive sequence fundamental voltage to correct the error, Simulation results show that the active and reactive component of positive sequence fundamental current and the active and reactive component of negative sequence fundamental current can be obtained rapidly and accurately.
Keywords
reactive power; current component; detecting error; instantaneous reactive power theory; ip-iq current detection method; negative sequence fundamental current; phase angle; positive sequence fundamental voltage; reactive component; Active filters; Equations; Hardware; Mathematical model; Phase locked loops; Power harmonic filters; Reactive power;
fLanguage
English
Publisher
ieee
Conference_Titel
Power and Energy Engineering Conference (APPEEC), 2012 Asia-Pacific
Conference_Location
Shanghai
ISSN
2157-4839
Print_ISBN
978-1-4577-0545-8
Type
conf
DOI
10.1109/APPEEC.2012.6306943
Filename
6306943
Link To Document