• DocumentCode
    3385401
  • Title

    Electrical performance of fiberglass crossarms aged in transmission line

  • Author

    Grzybowski, S. ; Jenkins, E.B.

  • Author_Institution
    Dept. of Electr. & Comput. Eng., Mississippi State Univ., MS, USA
  • fYear
    1992
  • fDate
    7-10 Jun 1992
  • Firstpage
    217
  • Lastpage
    221
  • Abstract
    The authors present the results of an investigation of the electrical performance of a 115-kV transmission line fiberglass crossarm. Crossarms removed from service and companion crossarms stored outdoors but not in service were examined. The evaluation of electrical performance was based on flashover voltage value at AC voltages and at standard lightning impulse voltages, measured under dry and wet conditions. The impulse voltage waveshape used in all the laboratory investigations was a standard 1.2/50-μs wave as described in IEEE Standard 4 and had positive polarity. The flashover voltages obtained showed no large difference in electrical strength between fiberglass crossarms removed from service and those stored outdoors
  • Keywords
    ageing; electric strength; flashover; insulation testing; insulators; power overhead lines; supports; 115 kV; AC voltage test; AC voltages; IEEE Standard 4; electrical performance; electrical strength; flashover voltage; impulse voltage waveshape; lightning impulse voltages; transmission line fiberglass crossarm; wet conditions; Aging; Flashover; Insulation testing; Insulator testing; Optical fiber devices; Optical fiber testing; Power transformer insulation; System testing; Transmission lines; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulation, Conference Record of the 1992 IEEE International Symposium on
  • Conference_Location
    Baltimore, MD
  • ISSN
    1089-084X
  • Print_ISBN
    0-7803-0649-X
  • Type

    conf

  • DOI
    10.1109/ELINSL.1992.247016
  • Filename
    247016