Abstract :
Using ATP / EMTP to simulate the single-phase ground fault on transmission line, then use the empirical mode decomposition (EMD) to decompose the fault phase voltage signal, and calculate sample entropy values of the intrinsic mode function (IMF) to determine it´s transient or permanent faults. When it is transient faults that the line can implement the successful adaptive Reclosing. Through a large number of line fault simulations show the effectiveness and practicality of the method.
Keywords :
entropy; power overhead lines; power supply quality; power system stability; power transmission faults; power transmission protection; ATP; EMTP; adaptive reclosing; empirical mode decomposition; entropy value; fault phase voltage signal; intrinsic mode function; permanent fault; sample entropy; single phase ground fault; single pole adaptive transmission reclosure; transient fault; transmission line; Circuit faults; Entropy; Inductors; Power transmission lines; Resistance; Transient analysis; EMD; Single-Pole Adaptive reclosure; permanent faults; sample entropy; transient faults;