    Study on the Operation of 10kV Arc-Suppression Coils in Distribution Network

  • Author

    Huang Songbo ; Su Qi ; Lu Tiecheng ; Mai Hong

  • Author_Institution
    Sch. of Electr. Eng., WHU, Wuhan, China
  • fYear
    2012
  • fDate
    27-29 March 2012
  • Firstpage
    1
  • Lastpage
    4
  • Abstract
    Since the way of arc-suppression coil grounding 10kV distribution network is in a high proportion. This paper study on the operation of the three types of arc-suppression coils, including phase control type, turns adjusting type, capacitive adjusting type, in 10kV distribution network. According to the typical parameters of the 10kV distribution network of 110kV substation, the EMTP-ATP was utilized to analyze the arc fault over-voltage, the arc-suppression coil dynamic response time when there is single-phase arc ground fault, and the Harmonic currents inputted to the power system. At the end, the three types of arc-suppression coil were made an objective comparison and evaluation in the aspects of the inhibition of over-voltage, dynamic response time and harmonic currents.
  • Keywords
    EMTP; arcs (electric); coils; dynamic response; earthing; overvoltage; phase control; power distribution faults; power system harmonics; substations; EMTP-ATP; arc fault over-voltage; arc-suppression coil grounding; capacitive adjusting coil; distribution network; dynamic response time; harmonic current; phase control coil; power system; single-phase arc ground fault; substation; turns adjusting coil; Coils; Grounding; Harmonic analysis; Power harmonic filters; Power system dynamics; Time factors;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power and Energy Engineering Conference (APPEEC), 2012 Asia-Pacific
  • Conference_Location
    Shanghai
  • ISSN
    2157-4839
  • Print_ISBN
    978-1-4577-0545-8
  • Type

    conf

  • DOI
    10.1109/APPEEC.2012.6307347
  • Filename
    6307347