    Overvoltage of 110kV, 220kV Transformer Neutral Point and Its Protection Analysis

  • Author

    Li Yining ; Liu Junyi ; Kuang Shi ; Xie Wenbing

  • Author_Institution
    Zhengzhou Electr. Power Co., Zhengzhou, China
  • fYear
    2012
  • fDate
    27-29 March 2012
  • Firstpage
    1
  • Lastpage
    4
  • Abstract
    In most of the 110kV and 220kV power grid, the neutral point insulation of the ungrounded transformer is vulnerable to be damaged. So the arrester and nod gap in paralleled are generally used in protecting the insulation. But there is some shortage of this protection method. In this paper, a simulation was done research the over voltage on neutral point, by using ATP, and the reason why the shortage exists was proposed. An improvement method to solve that problem was also referred, which is increasing the distance of rod gap and the rated voltage of MOA.
  • Keywords
    arresters; power grids; power transformer insulation; power transformer protection; ATP; MOA; arrester; nod gap; power grid; protection analysis; ungrounded transformer neutral point insulation; voltage 110 kV; voltage 220 kV; Discharges (electric); Insulation; Lightning; Mathematical model; Power transformer insulation; Transient analysis; Voltage control;