• DocumentCode
    3395842
  • Title

    HVDC with voltage source converters - a powerful standby black start facility

  • Author

    Jiang-Hafner, Ying ; Duchen, Hugo ; Karlsson, Michael ; Ronstrom, Leif ; Abrahamsson, Bernt

  • Author_Institution
    ABB AB, Power Syst., Ludvika
  • fYear
    2008
  • fDate
    21-24 April 2008
  • Firstpage
    1
  • Lastpage
    9
  • Abstract
    This paper deals with the black start function of VSC based HVDC. The voltage and frequency characteristics of VSC HVDC during different stages of network restoration will be described. The differences and similarities between the traditional black start units and VSC HVDC will be highlighted. Results by plots from field testing will be illustrated. The verification of expected performance by field testing indicates that HVDC made of voltage source converters is an ideal standby facility for black start and restoration of an ac grid, in addition to the normal function of power transmission with independent active and reactive power control.
  • Keywords
    HVDC power convertors; HVDC power transmission; power control; power grids; power transmission control; VSC HVDC; ac grid; frequency characteristics; network restoration; power transmission; powerful standby black start facility; reactive power control; voltage source converters; Converters; Frequency; HVDC transmission; Power conversion; Power generation; Power system restoration; Power transmission; Reactive power control; Testing; Voltage; HVDC; VSC; black start; restoration; transmission;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Transmission and Distribution Conference and Exposition, 2008. T&D. IEEE/PES
  • Conference_Location
    Chicago, IL
  • Print_ISBN
    978-1-4244-1903-6
  • Electronic_ISBN
    978-1-4244-1904-3
  • Type

    conf

  • DOI
    10.1109/TDC.2008.4517039
  • Filename
    4517039