Author_Institution :
Gen. Electr. Co., Salem, VA, USA
Abstract :
The description is given of a bidirectional 18-pulse voltage source converter utilizing gate turn-off thyristors (GTOs). The converter, which is rated at 10 MVA, has been placed in service to connect an energy storage battery to a utility grid. The converter is rated and controlled to operate in all four quadrants (discharge, charge, leading VArs, or lagging VArs) at the full 10 MVA rating. It is capable of independent, rapid control of real and reactive power with a transient response of 16 ms to changes in commanded value of real or reactive power. Thus it is usable as a reactive power controller (static VAr control), voltage control, frequency control, power system stabilizer, or as a real power peaking station. The author describes the design, construction, control, and application of the converter, and gives performance data taken at the installation.<>
Keywords :
power control; power convertors; power systems; secondary cells; thyristor applications; voltage control; 10 MVA; 10 MW; 16 ms; bidirectional 18-pulse voltage source converter; energy storage battery; frequency control; gate turn-off thyristors; power control; power system stabilizer; reactive power control; static VAr control; transient response; utility grid; voltage control; Batteries; Control systems; Energy storage; Fault location; Frequency control; Reactive power; Reactive power control; Thyristors; Transient response; Voltage control;