Title
Experience with 100% stator ground fault protection schemes
Author
Mozina, Charles J.
Author_Institution
Consultant with Beckwith Electr. Co., Largo, FL
fYear
2008
fDate
21-24 April 2008
Firstpage
1
Lastpage
7
Abstract
This paper discusses the experiences of several users with the application of three different 100% stator ground fault protection schemes. Two third-harmonic methods and a low frequency-injection method are included. This paper explains situations in which third-harmonic schemes work, and also the limitations of these schemes, which are not well understood by many relay engineers. It also discusses the use of a low-frequency injection scheme along with its limitations.
Keywords
electric generators; fault diagnosis; harmonic analysis; power generation protection; relay protection; generator protection; low frequency-injection method; relay engineers; stator ground fault protection schemes; two third-harmonic methods; Circuit faults; Digital relays; Fault location; Frequency; Grounding; Protection; Protective relaying; Stator windings; Tellurium; Voltage measurement; Generator; Generator Protection; Low-Frequency Injection; Multifunction Digital Relay; Stator Ground Fault; Third-Harmonic Method;