DocumentCode :
3398112
Title :
Simulation of PD location in power transformer based on Root Multiple Signal Classification method
Author :
Li, Yan-qing ; Xie, Qing ; Wang, Nan ; Xiang, Xin ; Lü, Fang-Cheng
Author_Institution :
Key Lab. of Power Syst. Protection & Dynamic Security Monitoring & Control, North China Electr. Power Univ., Baoding, China
fYear :
2009
fDate :
19-23 July 2009
Firstpage :
553
Lastpage :
556
Abstract :
Due to the heavy calculation and low estimation precision with little signal-to-noise (SNR) of MUSIC (multiple signal classification) algorithm in partial discharge location used ultrasonic phased array, in this paper, a new location method is proposed based on root-multiple signal classification (Root-MUSIC). Firstly, Root-MUSIC algorithm is used for direction of arrival estimating of PD source. Secondly, space location of PD source is realized by crossover location principle. Finally, the result of simulation based on 7 times 7 plane phased array model vertifies the correctness of the new method.
Keywords :
partial discharges; power transformers; signal classification; Root-MUSIC; crossover location; partial discharge location; plane phased array; power transformer; root multiple signal classification method; ultrasonic phased array; Accidents; Classification algorithms; Covariance matrix; Direction of arrival estimation; Eigenvalues and eigenfunctions; Multiple signal classification; Partial discharges; Phased arrays; Power transformers; Signal analysis; crossover location; partial discharge; root-MUSIC;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Properties and Applications of Dielectric Materials, 2009. ICPADM 2009. IEEE 9th International Conference on the
Conference_Location :
Harbin
Print_ISBN :
978-1-4244-4367-3
Electronic_ISBN :
978-1-4244-4368-0
Type :
conf
DOI :
10.1109/ICPADM.2009.5252369