DocumentCode
3399177
Title
A Parameter Modification Based Transmission Line Fault Location Method Using Single-Ended Current
Author
Liu, Yuping ; He, Zhengyou ; He, Wen
Author_Institution
Sch. of Electr. Eng., Southwest Jiaotong Univ., Chengdu, China
fYear
2012
fDate
27-29 March 2012
Firstpage
1
Lastpage
4
Abstract
This paper proposes a parameter modification based transmission line fault location algorithm using single-ended current, which requires less information than the method with two-ended current and avoids the effects of TA saturation or break. At the same time, considering the impacts of dynamic conditions on the parameters of transmission line, such as power oscillation , Parameter Modification Fault Locator(PMFL) based on Phasor Measurements is presented. Simulations with the help of PSCAD/EMTDC are done and the results allow us to make a conclusion that the proposed method has an effective performance on fault location at the cost of minor computation increase.
Keywords
fault location; phasor measurement; power transmission faults; power transmission lines; PSCAD-EMTDC; TA saturation; parameter modification-based transmission line fault location method; phasor measurements-based PMFL; phasor measurements-based parameter modification fault locator; power oscillation; single-ended current; transmission line parameters; two-ended current; Fault location; Heuristic algorithms; Power system dynamics; Power transmission lines; Resistance; Transmission line measurements; Voltage measurement;
fLanguage
English
Publisher
ieee
Conference_Titel
Power and Energy Engineering Conference (APPEEC), 2012 Asia-Pacific
Conference_Location
Shanghai
ISSN
2157-4839
Print_ISBN
978-1-4577-0545-8
Type
conf
DOI
10.1109/APPEEC.2012.6307649
Filename
6307649