DocumentCode :
3399193
Title :
Case study: Adaptative overcurrent protection scheme applied to an industrial plant with cogeneration units
Author :
Soares, Antonio H M ; Vieira, Jose C M
Author_Institution :
Sch. of Eng., USP, Sao Carlos
fYear :
2008
fDate :
21-24 April 2008
Firstpage :
1
Lastpage :
5
Abstract :
Although digital protection has been widely employed in power system industry, many protection practices are still the same employed to electromechanical relays. Consequently, the potentialities and benefits of digital relays are not fully explored. In this context, this work presents the advantages of digital protection to coordinate overcurrent relays in an industrial plant with three cogeneration units, resulting in three operating scenarios. It is shown that conventional practices did not result in an efficient solution and an adaptative protection scheme was proposed, which guaranteed overcurrent coordination for all the considered operating scenarios.
Keywords :
cogeneration; industrial plants; overcurrent protection; power generation protection; relay protection; adaptative overcurrent protection scheme; cogeneration units; coordinate overcurrent relays; digital protection; digital relays; electromechanical relays; industrial plant; overcurrent coordination; power system industry; Circuit faults; Cogeneration; Digital relays; Hazards; Industrial plants; Load flow; Power system protection; Power system relaying; Power system reliability; Protective relaying; Digital protection; cogeneration; overcurrent coordination;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Transmission and Distribution Conference and Exposition, 2008. T&D. IEEE/PES
Conference_Location :
Chicago, IL
Print_ISBN :
978-1-4244-1903-6
Electronic_ISBN :
978-1-4244-1904-3
Type :
conf
DOI :
10.1109/TDC.2008.4517230
Filename :
4517230
Link To Document :