• DocumentCode
    3399193
  • Title

    Case study: Adaptative overcurrent protection scheme applied to an industrial plant with cogeneration units

  • Author

    Soares, Antonio H M ; Vieira, Jose C M

  • Author_Institution
    Sch. of Eng., USP, Sao Carlos
  • fYear
    2008
  • fDate
    21-24 April 2008
  • Firstpage
    1
  • Lastpage
    5
  • Abstract
    Although digital protection has been widely employed in power system industry, many protection practices are still the same employed to electromechanical relays. Consequently, the potentialities and benefits of digital relays are not fully explored. In this context, this work presents the advantages of digital protection to coordinate overcurrent relays in an industrial plant with three cogeneration units, resulting in three operating scenarios. It is shown that conventional practices did not result in an efficient solution and an adaptative protection scheme was proposed, which guaranteed overcurrent coordination for all the considered operating scenarios.
  • Keywords
    cogeneration; industrial plants; overcurrent protection; power generation protection; relay protection; adaptative overcurrent protection scheme; cogeneration units; coordinate overcurrent relays; digital protection; digital relays; electromechanical relays; industrial plant; overcurrent coordination; power system industry; Circuit faults; Cogeneration; Digital relays; Hazards; Industrial plants; Load flow; Power system protection; Power system relaying; Power system reliability; Protective relaying; Digital protection; cogeneration; overcurrent coordination;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Transmission and Distribution Conference and Exposition, 2008. T&D. IEEE/PES
  • Conference_Location
    Chicago, IL
  • Print_ISBN
    978-1-4244-1903-6
  • Electronic_ISBN
    978-1-4244-1904-3
  • Type

    conf

  • DOI
    10.1109/TDC.2008.4517230
  • Filename
    4517230